Product List
FN300 - Thermal Flow Switch with LED Digital Display
- 4 - digit LEDs
- Flow velocity / percentage display
- Wide measuring range
- Measuring span programmable
- PNP / NPN programmable
- 4..20mA/0…20mA/1…5V/0…5V output programmable
- Rotatable indicator
- Easy to read, robust display
Applications
- Hydraulic system
- Pump protection
- Cooling system
- Venting systems
- Water treatment
- Leak monitoring
- Lubrication system
- Machinery manufacture
- Equipment manufacture
- Engineering project
Specifications
Measuring range | |
Water | 1...200cm/s |
Oil | 3…300cm/s |
Air | 20…2000cm/s |
Applicable medium | water, oil and gas which is compatible with 316 stainless steel |
Repeatability | 1%@<0.6m/s; 3%@<1.5m/s; 10%@>1.5m/s ( for water) |
Pressure rating | 100 bar (200bar selectable) |
Initialization time | 1 … 8s |
Response time | 2s typical |
Power supply | 24±10%Vdc |
No-load current consumption | ≤100mA (power supply 24Vdc) |
Switching output | |
Output | Push-pull(compatible with PNP / NPN) NC / NO configurable |
S1,S2 output current | <500 mA |
Voltage drop | <1V |
Current analog output | |
Output | 3-wire 0...20mA / 4...20mA programmable |
Load RA | RA≤0.5Kohm |
Voltage analog output | |
Output | 3-wire 0...5V / 1...5V programmable |
Load RA | RA>10Kohm |
Wiring Protection | Reverse polarity, Overvoltage and Short-circuit |
Display | |
Design | 8mm height, red 4-digit LED |
Display range | -1999...9999 |
Temprature | |
Operating | -40…85℃ |
Medium | -20…85℃, up to130℃(not more than 2 hours) |
Materials | |
Housing | 304 stainless steel |
Probe | 304 stainless steel/316 stainless steel(for the sanitary ) |
Protection class | IP67 |
Electrical connection | M12 x 1 plug |